Sizing a Diffuser From Your Design Rates: Spigot Diameters, m³/h and Slot Count

Sizing a Diffuser From Your Design Rates: Spigot Diameters, m³/h and Slot Count

You have a design rate in litres per second and a ceiling plan. You need a spigot diameter, a diffuser length and a slot count. This is the arithmetic, in order, with the numbers written out — including the one decision people consistently get wrong: when to step up from two slots to three.

Before you start

Ventmann publishes rates in m³/h. UK design rates are usually in l/s. The conversion is the whole of the difficulty: l/s × 3.6 = m³/h. So 15 l/s is 54 m³/h; 30 l/s is 108 m³/h.

Step 1 — Get the rate per outlet, not per room

The design rate is for the space. The diffuser is sized for what passes through it. If a 54 m³/h bedroom supply is split across two diffusers for throw reasons, each one is sized at 27 m³/h — and two small diffusers behave very differently from one large one.

Typical UK residential starting points, converted:

Space Typical rate m³/h
WC / cloakroom extract 6 l/s 22
Bathroom / shower room extract 15 l/s 54
Kitchen extract (with hood) 13 l/s 47
Kitchen / utility extract (no hood) 30 l/s 108
Bedroom MVHR supply 8–13 l/s 29–47
Living room MVHR supply 13–20 l/s 47–72
Office, per person 10 l/s 36
Comfort cooling branch, small room varies with load 150–350

Indicative only — always work from the project's own ventilation strategy and the current Approved Document F or the relevant CIBSE guidance.

Step 2 — Pick the spigot from duct velocity

The spigot size is set by how fast you are willing to let air move in the last leg of duct. Keep it low and the system is quiet and the pressure drop is small; push it high and you save space but generate noise exactly where you cannot attenuate it.

Workable velocities for the final branch into a diffuser:

  • 2.5–3 m/s — bedrooms, hotel rooms, consulting rooms, anywhere with an NR target. Quiet.
  • 3–4 m/s — general residential and office. The normal working band.
  • 4–5 m/s — extract, plant areas, circulation. Acceptable where noise is not critical.

Which gives you this table. Find your m³/h in the body of the table and read off the diameter.

Spigot Area @ 2.5 m/s @ 3 m/s @ 4 m/s @ 5 m/s
Ø75 0.0044 m² 40 48 64 80
Ø100 0.0079 m² 71 85 113 141
Ø125 0.0123 m² 110 133 177 221
Ø160 0.0201 m² 181 217 290 362
Ø200 0.0314 m² 283 339 452 565

All figures m³/h, rounded. Derived from Q = A × v × 3600.

Worked example. A bedroom supply at 13 l/s = 47 m³/h, in a house where the client has already complained about MVHR noise.

At 2.5 m/s a Ø75 carries 40 m³/h — not quite enough. At 3 m/s it carries 48 — adequate but with nothing in hand. Step up to Ø100 and you are at 1.7 m/s, which is silent, or to Ø125 if the duct run is long and you want the pressure drop back. On a GTG box the available knock-outs are Ø75, Ø125 and Ø160 — so the answer here is Ø125, reduced from the branch if necessary with a pressed reducer.

Step 3 — Length and slot count: the real decision

The spigot moves the air to the diffuser. The length and slot count decide what the air does once it gets into the room — how far it throws, how fast it is at head height, and how loud the slot is.

Both Line and Performance Line come in 625, 1000 and 1250 mm, each with 1, 2 or 3 slots. That gives nine combinations and two ways to add free area for a given flow rate: make it longer, or add slots.

They are not equivalent

Adding length spreads the air over a wider arc of the room and shortens throw. Good for wide rooms and for getting a diffuser to line up with a ceiling joint or a lighting run.

Adding slots increases free area without changing the run. It drops face velocity — which drops noise and drops throw — while keeping the architectural line the same width in plan.

So the question "2 slot or 3 slot?" is really "do I need more free area in the same visual length, and am I happy to lose throw?"

When to go 2 slot, and when to go 3

Condition 1 slot 2 slot 3 slot
Low rate, small room (<60 m³/h) ✔ default over-specified no
Mid rate (60–180 m³/h) only if run is long ✔ default if noise critical
High rate (>180 m³/h) no at 1250 mm only ✔ default
Comfort cooling, occupants below no acceptable ✔ preferred
NR 25 or tighter no marginal ✔ preferred
Deep room, throw needed ✔ longest throw good throw falls away
Extract only ✔ cheapest adequate if rate demands rarely needed
Ceiling >3 m ✔ needs the velocity good air may not reach occupants

The mistake worth avoiding: specifying 3 slots everywhere because it sounds like the premium option. On a high ceiling or a deep room, three slots drop the discharge velocity so far that the air separates from the ceiling early, falls short, and leaves a stagnant zone at the far end. More free area is not automatically better — it is a trade against throw.

Step 4 — Slot gap: 12 mm or 18 mm

Line is offered with a 12 mm or an 18 mm slot gap; Performance Line uses a 20 mm gap with its curved profile. The 12 mm gap is the tighter architectural reveal and reads as a shadow line; the 18 mm gives you half as much free area again for the same run.

Practically: start at 12 mm if the aesthetic matters and the rate is modest. Move to 18 mm when the rate pushes face velocity up and you cannot lengthen the diffuser — usually because the ceiling detail or the joist spacing will not allow it.

Step 5 — Verify against the published data

Everything above gets you to a sensible shortlist fast. It does not replace the performance tables. Before the schedule goes out, put each selection through the Ventmann product selector, which filters the LINE, PLINE and PCIRCLE ranges on:

  • design flow rate in m³/h or l/s
  • maximum SPLA in dB(A)
  • total pressure drop Pt in Pa
  • maximum installation length in mm
  • number of slots

The full throw (X in metres), pressure drop, SPLA and effective area (Ak) tables for every configuration, supply and extract, are in the technical catalogue.

Step 6 — Carry the sizing through to the plenum

The spigot you chose in step 2 has to exist on the plenum box you specify in step 6. It does not always.

If the sizing lands on Ø200, the GTG is out and you are on a VTBOX whichever way the duct arrives. If it lands on Ø75, only the GTG offers it. Width code (A, B or C) must match the diffuser's slot count, and the plenum length must match the diffuser length.

If you are using Performance Circle instead

The Performance Circle skips most of this. It connects directly to a Ø125, Ø160 or Ø200 spigot, no plenum, with duties up to around 200 m³/h on the Ø160 and around 300 m³/h on the Ø200. Size the spigot from the table in step 2, choose 1 or 2 slot, and you are done.

The sizing sheet, condensed

  1. Rate per outlet in l/s → × 3.6 → m³/h
  2. Choose branch velocity (2.5–3 quiet, 3–4 normal, 4–5 extract) → read spigot off the table
  3. Choose length from the ceiling layout; choose slot count from rate, noise target and throw
  4. Choose slot gap: 12 mm for the detail, 18 mm for the free area
  5. Verify in the product selector against SPLA and Pt
  6. Match plenum: entry direction, spigot availability, width code, length

Send us the schedule

Give us the room-by-room design rates and the ceiling plan and we will return a sized diffuser and plenum schedule with part numbers, priced. No charge.